Notes: All units new. See "Info" page for warranty details. All
Prices FOB Houston, TX.Shipping & taxes not include in price.
Voltage Monitors from MPE
Single Phase Motor Protection
The Over/Under Voltage Monitor is used to protect single phase
equipment that is required to operate between two voltage limits. In a
normal voltage environment, the internal relay will energize and the LED
will illuminate allowing normal operation. Abnormal voltage conditions will
cause the internal relay to de-energize and the LED to turn off.
UL listed models require use of an RB08 or RB08-PC socket.
UL File No.
|
#E101681
|
Operating Voltage (AC)
|
120V
|
Relay Type
|
DPDT
|
Base Terminal Configuration
|
Plug in 12 Pin Rectangular
|
Under Voltage Trip
|
-15% of Setting
|
Under Voltage Reset
|
-12% of Setting
|
Over Voltage Trip
|
+15% of Setting
|
Over Voltage Reset
|
+12% of Setting
|
Phase Unbalance Trip
|
7% with 5 Second Trip Delay
|
Phase Unbalance Reset
|
6%
|
Trip Delay
|
5 sec.
|
Reset Delay
|
2 sec.
|
Voltage Range
|
100-130V
|
Output Rating at 240V (AC)
|
10A Resistive 6A Inductive
|
Operating Temperature
|
-40 to +50C
|
Storage Temperature
|
-45 to +85C
|
Enclosure Material
|
White Lexan
|
Base Material
|
Phenolic
|
Protects Against
|
Over/Under Voltage Rapid Load Cycling
|
|
Part No
|
Options
|
Sale Price
|
004-120-1212
|
Standard
|
|
004-120-1212OV
|
Over Voltage
|
|
004-120-1212G5
|
5 Second Reset Delay
|
|
004-120-1212G10
|
10 Second Reset Delay
|
|
004-120-1212G20
|
20 Second Reset Delay
|
|
004-120-1212G30
|
30 Second Reset Delay
|
|
004-120-1212G60
|
60 Second Reset Delay
|
|
|